W-M2B101

2 Channels 4-in-1 Analog Input Module
Neu

W-M2B101

2 Channels 4-in-1 Analog Input Module
Neu
Features
  • 2-Ch Analog Input
  • 4-in-1 Analog Input Module (voltage /current / thermocouple /RTD)
  • Channel Independent Configuration
Dem Vergleich zufügen
The W-M2B101 is a 2 Channels 4-in-1 Analog Input Module (Voltage / Current / Thermocouple / RTD) which provides industries who might only need less channel for data acquisition.
Technische Daten

General

Power Requirement 10 ~ 36 VDC
Power Consumption 1.2 W @ 24V
Watchdog Timer Yes
Connector Plug-In Terminal Block (#16~30 AWG)
Temperature (Operating) -25~70℃
Temperature (Storage) -30~75℃
Humidity 5~95%
Interface RS-485
Communication Protocol Modbus RTU
Communication Speed Serial: From 2.4 to 115.2 kbps
Communication Distance Serial: 1.2 km at 9.6 kbps
Isolation Protection 2500 VDC

I/O Specifications

Channels 2 Channels
High Voltage Input ±5V, ±10V, 0 ~ 5V, 0 ~ 10V
Low Voltage Input ±100mV, ±500mV, ±1V, 0~100mV, 0~500mV, 0 ~ 1V
Current Input ±20mA, 4~20mA, 0~20mA
TC Sensor Input J, K, T, E, R, S, B, N
RTD Sensor Types Platinum 100 α= 0.00385 (IEC) -200 ~ 600℃
Platinum 100 α= 0.00392 (JIS) -200 ~ 600℃
Platinum 1000 α= 0.00385 (IEC) -200 ~ 600℃
Disconnection Detection 4 ~ 20 mA, all T/C , all RTD
Channel Independent Configuration Yes
Sampling Rates 2 samples /second
Resolution 16-bit
Accuracy ±0.1% FSR
Input Impedance Voltage: 100 KΩ
Current: 120 Ω
Span Drift ±25 ppm/℃
Zero Drift ±6 μV/℃
Input Voltage Protection ±36V for Input Terminal: U+
±12V for Input Terminal: M+, M-, S-
Input Current Protection 50 mA for Input Terminal: I+